Case · Water and sanitation

Unacceptable risk reduced to zero without replacing the installed automation base

OT/ICS Risk Assessment at two water treatment plants and the operational control center of a water and sanitation company. Anonymized data.

Talk to an expert

Vulnerability is not risk

The central question of the Risk Assessment is not which vulnerabilities exist, but what physically happens to the process if an automation function is compromised. It is the adaptation of established process risk analysis techniques, such as HAZOP and LOPA, to the cyber domain: the Cyber-PHA of ISA/IEC 62443-3-2.

The vulnerability scan still exists, but it serves as evidence for likelihood, not as the final result. Priority is now defined by physical impact, in a language the board understands.

Scope

What was assessed

2 water treatment plants, plus the operational control center
26 automation functions, from the PLC to the MQTT broker
96 risk scenarios assessed
208 assets inventoried, 40 of them OT
Evidence

Three sources feed the likelihood of each function

  • Asset inventory: 208 assets identified, 40 of them OT, including 29 PLCs and 3 HMIs, by Purdue level, firmware and rack/slot. Passive collection, without touching the process.
  • Vulnerabilities: 20 assets with unpatched CVEs, 10 at end of life, 4 with multiple network interfaces and USB connected on 3.
  • NIST SP 800-82 · CSET: 102 gaps ranked by SAL: 41% of the questions met and 24% not met.
Likelihood Vulnerabilities NIST · CSET Inventory
Methodology

Five steps, two workshops

  1. 01

    Scope and stakeholders

    System under consideration, zones, conduits, specialists and those responsible for acceptance.

  2. 02

    Reference threat actor

    Profile from TA1 to TA5, approved by consensus, without underestimating or inflating the risk.

  3. 03

    Functions and consequences

    Automation functions by Purdue level and consequences identified through guiding questions.

  4. 04

    Severity and likelihood

    Severity without defenses in four dimensions and likelihood by an objective rubric.

  5. 05

    Risk, controls and residual risk

    Risk register, controls linked to ISA/IEC 62443-3-3 and recalculation of the residual risk.

How risk is measured

Severity × likelihood, from 1 to 25

Risk rangeClassificationWhat to do
17 to 25UnacceptableImmediate action; cannot be accepted
9 to 16Conditionally tolerableDocumented controls with a deadline
1 to 8AcceptableMonitor, no mandatory action

Likelihood by equipment category: attractiveness 15%, capability 25%, exposure 35% and defense 25%. Severity is assessed as if no controls existed, and the criticality of each function comes from its worst scenario.

Result

Before and after the controls

The chosen reference actor was TA3: organized crime with knowledge of industrial systems, the most likely for the sector. Plant A had 8 unacceptable scenarios, with a risk of 20 out of 25.

20 highest risk at plant A before the controls; afterwards, 10
16 highest risk at plant B before the controls; afterwards, 4
0 unacceptable scenarios after the controls
15 controls prioritized by protection value

At plant A, 14 scenarios were awaiting data and were left out of the comparison.

Controls

15 controls by protection value

Each control was linked to the system requirements of ISA/IEC 62443-3-3 and to the target security level (SL-T), separating what is configuration from what is acquisition. The sequence matters: segmentation first.

Priority 1 · 6 controls

Close the attack path

  • Segmentation into zones and conduits
  • MFA and individual identity
  • Continuous OT monitoring
  • Physical port and removable media control
  • Elimination of wireless and 4G
  • Secure protocol gateway
Priority 2 · 8 controls

Directly reduce the likelihood

  • Jump server in an industrial DMZ
  • Temporary credentials for third parties
  • TLS and authentication on the MQTT broker
  • Per-topic ACL on MQTT
  • Vulnerability management
  • Formal change control
  • Least privilege in the supervisory system
  • Assisted manual operation
Priority 3 · 1 control

Shorten the downtime

  • Verified backup and recovery plan
Target architecture

From the current topology to the target architecture

Process data leaves IT

SCADA servers, SCADA Mobile and the MQTT broker leave the corporate data center and move to the industrial network.

A DMZ that terminates and reopens

The industrial DMZ now breaks every connection, with an MQTT relay, a SCADA Mobile proxy and patch/antivirus.

Remote access in two hops

Central access in the DMZ and local access in the industrial network; third parties no longer reach the OT network directly.

Detection with IDS and SPAN

Industrial IDS with traffic mirroring on the control switch, to see what cannot be seen today.

Deliverables

What the company received

Diagnosis

  • Complete Cyber-PHA Functions, scenarios, severity, likelihood and residual risk.
  • Asset inventory IT and OT by Purdue level, manufacturer and firmware.
  • Vulnerabilities CVEs, end of life, multiple interfaces and USB.
  • NIST SP 800-82 Compliance via CSET, with ranked gaps.

Plan

  • Executive report A board-level reading, with investment guidance.
  • SL-T and controls ISA/IEC 62443-3-3 requirements by security level.

Architecture

  • Current topology Today’s architecture by Purdue level. leads to
  • Target topology Zones, functional DMZ and detection.